| Boiler Model | DIM. | 350 | 400 | 500 | 625 | 750 | 1000 | 1250 | 1500 | 1750 | 2000 | 2500 | 3000 | 3500 | 3750 | 4000 | 4500 | 5000 | Boiler Model |
| Lengths: Overall Shell Base Front Plate To Skid Extension Rear Plate To Center Line of Stack Front Of Base To End of Burnter (IC Only) Front Plate To Nozzle |
A B C D E F G |
165 134 125 26 2 12 43 |
178 147 138 26 2 15 43 |
206 174 165 26 2 15 47 |
189 156 145 26 2 15 47 |
215 182 170 26 2 15 55 |
224 176 176 40 2 21 54 |
258 210 210 40 2 17 54 |
274 226 222 40 2 19 63 |
303 255 253 40 2 19 63 |
268 218 215 40 2 22 67 |
312 262 259 40 2 25 67 |
318 267 268 40 2 22 74 |
299 248 240 40 2 22 64 |
314 263 255 40 2 - 64 |
328 277 269 40 2 - 64 |
325 266 266 48 2 - 66 |
350 290 291 49 2 - 73 |
Lengths: Overall Shell Base Front Plate To Skid Extension Rear Plate To Center Line of Stack Front Of Base To End of Burnter (IC Only) Front Plate To Nozzle |
| Widths: Overall Centerline To Lagging Centerline To Water Column Over Jacket Base Width Outside Base Width Inside |
H I J K L M |
72 33 39 66 50 42 |
72 33 39 66 50 42 |
72 33 39 66 50 42 |
80 36 1/2 43 1/2 73 50 1/2 42 1/2 |
80 36 1/2 43 1/2 73 50 1/2 42 1/2 |
89 41 1/2 47 1/2 83 65 1/2 57 1/2 |
89 41 1/2 47 1/2 83 65 1/2 57 1/2 |
95 44 1/2 50 1/2 89 70 1/2 62 1/2 |
95 44 1/2 501/2 89 70 1/2 62 1/2 |
107 50 57 100 80 72 |
107 50 57 100 80 72 |
114 53 61 106 87 77 |
122 57 65 114 87 77 |
122 57 65 114 87 77 |
122 57 65 114 87 77 |
129 61 68 122 87 77 |
129 61 68 122 87 77 |
Widths: Overall Centerline To Lagging Centerline To Water Column Over Jacket Base Width Outside Base Width Inside |
| Connections: Feedwater - Right/Left Auxiliary Conn - Right Surface Blowoff - Right Auxiliary Conn - Top Stack Outlet O.D. High Pressure Steam Nozzle Blowdown Front Blowdown Rear Low Pressure Steam Nozzle Drain: Front Drain: Rear |
R S T U V W X Y W X Y |
1 1/4 1 1 1 1/2 15 7/8 3 - 1 1/2 6 * - 1 1/2 |
1 1/4 1 1 1 1/2 15 7/8 3 - 1 1/2 6 * - 1 1/2 |
1 1/4 1 1 1 1/2 15 7/8 4 ** - 1 1/2 6 * - 1 1/2 |
1 1/4 1 1 2 17 7/8 4 ** - 1 1/2 6 * - 1 1/2 |
1 1/4 1 1 2 17 7/8 4 ** - 2 6 * - 2 |
2 1 1 2 19 7/8 6 ** 2 2 8 * 2 2 |
2 1 1 2 19 7/8 6 ** 2 2 8 * 2 2 |
2 1 1 2 23 7/8 6 ** 2 2 10 * 2 2 |
2 1 1 2 23 7/8 6 ** 2 2 10 * 2 2 |
2 1 1 2 23 7/8 6 ** 2 2 12 * 2 2 |
2 1 1 2 23 7/8 8 ** 2 2 12 * 2 2 |
2 1 1 2 25 7/8 8 ** 2 2 12 * 2 2 |
2 1 1 2 25 7/8 8 ** 2 2 12 * 2 2 |
2 1 1 2 25 7/8 8 ** 2 2 12 * 2 2 |
2 1 1 2 25 7/8 8 ** 2 2 12 * 2 2 |
2 1 1 - 25 7/8 8 2 2 14 22 |
2 1 1 - 25 7/8 8 2 2 14 22 |
Connections: Feedwater - Right/Left Auxiliary Conn - Right Surface Blowoff - Right Auxiliary Conn - Top Stack Outlet O.D. High Pressure Steam Nozzle Blowdown Front Blowdown Rear Low Pressure Steam Nozzle Drain: Front Drain: Rear |
| Access Openings: Handholes High Pressure Low Pressure Manway 12x16" High Pressure Low Pressure |
Z ZZ |
5 6 1 - |
5 6 1 - |
5 6 1 - |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
5 5 1 1 |
Access Openings: Handholes High Pressure Low Pressure Manway 12x16" High Pressure Low Pressure |
| Minimum Clearances: Tube Removal front Rear Door Swing Rear |
TF DR |
99 14 |
111 14 |
139 14 |
121 14 |
146 14 |
138 22 |
172 22 |
182 22 |
211 22 |
174 21 |
218 21 |
220 21 |
201 24 |
216 24 |
230 24 |
220 24 |
244 24 |
Minimum Clearances: Tube Removal front Rear Door Swing Rear |
| Minimum Boiler Room Length Allowing For Door Swing And Tube Removal dimensions BF/DW Include 3'-0" Clearance At Rear of Boiler | |||||||||||||||||||
| Tube Removal Front Thru Door or Window |
BF DW |
269 206 |
294 219 |
349 246 |
313 228 |
364 254 |
350 248 |
418 282 |
444 298 |
502 327 |
428 290 |
516 334 |
523 339 |
485 371 |
515 335 |
543 349 |
522 346 |
570 371 |
Tube Removal Front Thru Door or Window |
| Boiler Model | DIM. | 350 | 400 | 500 | 625 | 750 | 1000 | 1250 | 1500 | 1750 | 2000 | 2500 | 3000 | 3500 | 3750 | 4000 | 4500 | 5000 | Boiler Model |
| Note | * 150 PSIG RF Flange | All Dimension are approximate & may be used for layout. Superior Boiler Works, Inc. reserves the right to change dimensions due to product revisions or job requirements. | Note | ||||||||||||||||
| ** 300 PSIG RF Flange | |||||||||||||||||||
![]() |
![]() |