osage_dimensional

Cisco Boiler Service Co., Inc.

Osage Dimensional Data

Back to main page:

Back one page:

Boiler Model DIM. 75 100 124 150 201 260 306 364 441 508 624 751 897 1021 1245 1513 1788 Boiler Model
Lengths:
Overall
Shell
Base
Front Plate To
Base Extension
Front Plate To Center
Line of Supply Nozzle
Front of Base T0
End of Burner
Gordon-Platt
Industrial Comb.
Rear Plate To Center
Line Stack Connection

A
B
C

D

E
-
F
-
-
-
G

78
37 1/2
67

26

11
-
-
3
-
-
6 1/8

90
49 1/2
77

26

16 1/2
-
-
3
-
-
6 1/8

85
42 1/2
70 3/4

26

11
-
-
6
12
-
6 15/16

92
51
78

26

20
-
-
6
12
-
6 15/16

108
67 1/2
95

26

20
-
-
6
12
-
6 15/16

104
60
87 1/2

28

25
-
-
4
13
-
8 7/16

115
70 1/2
100

28

31
-
-
4
13
-
8 7/16

130
84
114

28

31
-
-
4
13

8 7/16

137
82 1/2
116 1/2

31

29 1/2
-
-
-
8
-
9 1/16

148
94
128

31

37
-
-
3
11
-
9 1/16

168
114
148

31

37
-
-
3
12
-
9 1/16

188
136
167 1/2

31

50
-
-
8
17
-
9 1/16

176
117
152 1/2

34

44
-
-
6
11
-
12

193
134
170

34

50
-
-
4
12
-
12

208
146
184

34 1/2

45
-
-
7
19
-
12

237
175
213

34 1/2

45
-
-
7
22
-
12

231
162
202

37

55
-
-
4
22
-
14 1/2
Lengths:
Overall
Shell
Base
Front Plate To
Base Extension
Front Plate To Center
Line of Supply Nozzle
Front of Base T0
End of Burner
Gordon-Platt
Industrial Comb.
Rear Plate To Center
Line Stack Connection
Widths:
Overall
Centerline To
Lagging
Over Jacket
Base Width Outside
Base Width Inside

H

I
J
K
L

44

18 1/4
36 1/2
38 1/2
30 1/2

44

18 1/4
36 1/2
38 1/2
30 1/2

50

20 3/4
41 1/2
42 1/4
34 1/4

50

20 3/4
41 1/2
42 1/4
34 1/4

50

20 3/4
41 1/2
42 1/4
34 1/4

58

25
50
51
43

58

25
50
51
43

58

25
50
51
43

65

28
56
57
49

65

28
56
57
49

65

28
56
57
49

65

28
56
57
49

70 1/2

30 3/4
61 1/2
63
55

70 1/2

30 3/4
61 1/2
63
55

76

33 1/4
66 1/2
68 1/2
60 1/2

76

33 1/4
66 1/2
68 1/2
60 1/2

80

36 1/4
72 1/2
73 1/2
65 1/2
Widths:
Overall
Centerline To
Lagging
Over Jacket
Base Width Outside
Base Width Inside
Heights:
Overall
Base To Stack Conn
Floor To Return
Centerline
Height Of Runner

M
N

O
P

64
46

8
4

64
46

8
4

71
53 1/2

8 1/2
4

71
53 1/2

8 1/2
4

71
53 1/2

8 1/2
4

77
60

9
4

77
60

9
4

77
60

9
4

93
70

12 1/4
6

93
70

12 1/4
6

93
70

12 1/4
6

93
70

12 1/4
6

111
85

13 3/4
6

111
85

13 3/4
6

115
87 1/2

14
6

115
87 1/2

14
6

129
109 3/4

14
6
Heights:
Overall
Base To Stack Conn
Floor To Return
Centerline
Height Of Runner
Connections:
Steam Outlet
Feed Water
Blowdown
Inspection (3)
Stack Conn. OD.

Q
R
S
T
U

3
3
2
2
7 7/8

3
3
2
2
7 7/8

3
3
2
2
9 7/8

3
3
2
2
9 7/8

4
4
2
2
9 7/8

4
4
2
2
11 7/8

4
4
2
2
11 7/8

4
4
2
2
11 7/8

6 *
6 *
2 1/2
2 1/2
15 7/8

6 *
6 *
2 1/2
2 1/2
15 7/8

6 *
6 *
2 1/2
2 1/2
15 7/8

6 *
6 *
2 1/2
2 1/2
15 7/8

8 *
8 *
2 1/2
2 1/2
17 7/8

8 *
8 *
2 1/2
2 1/2
17 7/8

8 *
8 *
2 1/2
2 1/2
19 7/8

8 *
8 *
2 1/2
2 1/2
19 7/8

10 *
10 *
2 1/2
2 1/2
19 7/8
Connections:
Steam Outlet
Feed Water
Blowdown
Inspection (3)
Stack Conn. OD.
Access Openings:
Handholes 3" x 4"
Manway 12" x 16"

V
W

3
-

3
-

3
-

3
-

3
-

3
-

3
-

3
-

3
-

3
-

3
-

3
-

3
-

3
-

3
1

3
1

3
1
Access Openings:
Handholes 3" x 4"
Manway 12" x 16"
Minimum Clearances:
Tube Removal - Front

TF

34 1/2

46 1/2

40

48 1/2

64 1/2

57 1/2

67 1/2

81 1/2

77

88 1/2

108 1/2

130 1/2

110

127

139

168

153 1/2
Minimum Clearances:
Tube Removal - Front
Minimum Boiler room Length - Allowing For Tube Removal. BF Includes 3' - 0" Clearance At Rear.
Tube Removal - Front BF 127 151 139 156 189 176 197 224 226 249 289 332 296 331 356 414 430 Tube Removal - Front
  Dimension DW Includes 3' - 0" Clearance At Front And Rear.  
Thru Door or Window DW 153 165 163 171 187 182 192 206 209 223 243 271 254 269 287 316 307 Thru Door or Window
Boiler Model DIM. 75 100 124 150 201 260 306 364 441 508 624 751 897 1021 1245 1513 1788 Boiler Model
Note: * 150 PSIG RF Flange All dimensions are approximate and may be used for layout. Superior Boiler Works, Inc. reserves
the right to change dimensions due to product revisions or job requirements.
Note:



To Top Of Page: