lnd/seriesburners

Cisco Boiler Service Inc., Co

Industrial Combustion Burners

LND/Series Product Information

Back to main page:


42,54,63

84S, 84P, 105

145S, 145P, 175

210,252,300

315, 336

378, 420



To End of Page:

The LND/Series gas, liquid fuel, and combination gas/liquid fuel burner is a forced draft packaged burner system. A backward curved aluminum impeller mounted in a machined housing provides combustion air for various furnace pressures or high altitude applications. The air housing is hinged for convenient inspection or service of the firing head components.
Liquid fuel firing features, Industrial Combustion's low pressure air atomizing design. A metering unit, rotary vane air compressor, and air atomizing nozzle are integral parts of the system. The positive displacement oil metering unit is not affected by changes in oil temperature or viscosity.
Efficient gas combustion is attainde by introducing gas through ports ahead of the diffuser providing superior mixing of gas and air. Excellent flame retention is assured at all firing rates.
Flue gas recirculation (FGR) is drawn through the burner blower assembly properly sized for the required NOx emission levels. An FGR control valve is positioned by the FGR system to provide FGR at all firing rates. An FGR shutoff valve is placed in the FGR line as part of a safety system. This shutoff valve prevents combustible gases from being drawn into the boiler furnace prior to pilot and main flame ingition. Proper operation of this system is proven by three (3) electrical saftey interlocks. The system is equipped with ANSI flanges to allow easy installation into the FGR piping
High turndown capability on all fuels assures smooth starts and response to wide loade demands. Maximum effiency is achieved throughout the firing range. Convenient control switches permit selection of fixed rate or fully modulation operation.



A simple flip of a switch, on a Gas/Oil combinationburner, allows you to fire on one fuel or the other. No burner modifications or readjustments are required when changing fuels.
Listed by Underwriter Laboratory, CSD-1, I.RI., F.M., C.S.A. and other regulator agency control options are available. Every I.C. burner is assembled, wired, and tested at the factory. Compressor modules and main gas train components are shipped loose.



U.L. Standard Equipment
A. Controls E. Other Equipment
1. 120/1/60 control circuit 1. 3450 rpm blower motor and aluminum impeller
2. Burner mounted control panel 2. Burner mounting flange
3. Motor starter(s) 3. Refractory combustion cone and gasket
4. Panel signal lights (4) (See Note 4) 4. Hinged, swing-away air housing
5. Full Modulation with manual potentiometer 5. Rotary air damper w/silencer
6. Fuel changeover switch (combination gas/oil models) 6. Bolt On Firing head
7. Flame safeguard controls (see Note 1) 7. Gas manifold is standard on all oil burners for future gas firing
8. Combustion air proving switch 8. Cam Trim, U.L. listed
9. High fire air interlock switch F. Optional Equipment
B. Oil System 1. Plant atomizing air system using IC air regulating assembly
1. Burner mounted oil metering system 2. Steam atomization system using IC steam regulating assembly
2. Burner mounted integral atomizing air compressor (Except LNDE, LNDEG) Notes -
3. Separate air compressor module (LNDE, LNDEG) 1. U.V. scanner standard. Lead sulphide and other controls optional. U.V. NOT recommended for #4 thru #6 oil.
4. Air/lube oil reservoir 2. All main gas line valves and accessories upstream of butterfly valve are shipped loose
5. Fuel oil strainer (burner) 3. Standard motor voltages are 208-230-460/3/60. Totally enclosed and 50 cycle motors are optional.
6. Oil solenoid valve 4. Signal lights: Power On, Main Fuel, Ignition, and Flame Failure.
7. S.S.O. oil solenoid valve with relief valve. 5. A separate oil circulating pump set is required for all oil and combination fuel burners. The burner mounted unit is an oil input metering device only.
8. High oil temperature switch, mounted (LNDM, LNDMG, LNDE, LNDEG) Ordering Information (Specify)
9. Low oil pressure switch (LNDE, LNDEG) 1. Burner voltage, phase and cycle (See Note 3)
10. Atomizing air interlock switch 2. Control Circuit Voltage (120/1/60)
11. Nozzle line heater w/cold oil lockout (LNDM, LNDMG, LNDE, LNDEG) 3. Burner model and actual firing rate
C. Main Gas System (See Note 2) 4. Flame Safeguard Control
1. Butterfly rate control valve 5. Special Code and/or Insurance Requirements
2. One motorized valve and solenoid valve (LND42 & 54) 6. Availble Gas Pressure
3. One motorized valve with closure interlock and one solenoid valve motorized (LND63)    
4. Gas shutoff cocks (2)    
5. Main gas regulator    
6. High and low gas pressure switches    
D. Gas Pilot System    
1. Gas-electric    
2. Shutoff Cock    
3. Separate pilot regulator and valve, 5 psi    



To Top of Page: