lndseries84s_84p_105

Cisco Boiler Service Inc., Co

Industrial Combustion Burners

LND/Series Product Information
Burner Sizes 84S, 84P, 105

Back to main page:

Back to LND Series Burners General Information

To: LND Series Dimensions For Burner Sizes 84S, 84P, 105


42, 54, 63

145S, 145P, 175

210,252,300

315, 336

378, 420









Capacities and Specifications Burner Size
84S 84P 105
Oil Input (U.S.G.P.H.)(See Note 1) 45 53 60
Gas Input (M.BT/HR.)(See Note 2) 6,300 7,350 8,400
Boiler Horsepower @ 80% EFF. (See Note 3) 150 175 200
Maximum Steam Capacity @ 80% EFF. 212 Deg F (LBS./HR.)(See Note 3) 5,177 6,039 6,902
Metering Unit & Compressor Module Motor HP LNDL, LNDLG Metering Integral Oil/Air Unit - 3 Phase 1 2 2
LNDM, LNDMG Metering Integral Oil/Air Unit - 3 Phase 2 2 2
LNDE, LNDEG Oil Metering Unit 3 - Phase 1/2 1/2 1/2
Air Compressor Module - 3 Phase 3 3 3
Nozzle Line Heater. LNDM, LNDMG, LNDE, LNDEG 5 KW 5 KW 5 KW
Circulating Loop Oil Pressure Requirements (P.S.I.G.) 15 15 15
Standard Gas Train Size (Inches) 2 1/2 2 1/2 3
Minimum Gas Pressure Requirements (Inches W.C.)(See Note 4) Train Inlet 14.9 20.7 2 PSI
Manifold 7.0 10.0 13.0
Blower Motor Horsepower (See Note 5) Model "S" 5 - -
Model "P" - 10 15
FGR Line Piping Size (Inches) 6 6 6
Recommended Combustion Chamber Dimensions (Inches) Length 65 65 74
Width 34 34 38
Centerline Height 16 16 19
Approx. Shipping Weight 1,150 1,200 1,300
Notes
1. Oil input based on No.2 oil at 140,000 Btu/gal
2. Gas input based on natural gas at 1,000 Btu/cu.ft and 0.60 specific gravity
3. Boiler overall efficiency of 80% estimated. Industrial Combustion does not guarantee overall boiler efficiency.
4. Gas pressures based on zero furnace pressure with standard U.L. train inlet. For total pressure required, add furnace pressure.
5. Impeller and motor H.P. is based on altitudes up to 2000 feet above see level. For impellers and motor sizes at higher altitudes, and 50 cycle applications, consult factory. For higher furnace pressures, consult factory. Standard motor voltages are 208-230-460/3/60.



Type of fuel determines the model designation.
Model Fuel
LNDG Gas
LNDL No. 2 Oil
LNDLG Gas/No. 2 Oil
LNDM No. 2 - 5 Oil
LNDMG Gas/No. 2 - 5 Oil
LNDE No. 2 - 6 Oil
LNDEG Gas No. 2 - 6 Oil



To Top of Page: