lndseries145s_145p_175

Cisco Boiler Service Inc., Co

Industrial Combustion Burners

LND/Series Product Information
Burner Sizes 145S, 145P, & 175

Back to main page:

Back to LND Series Burners General Information

To: LND Series Dimensions For Burner Sizes 145S, 145P, 175


42, 54, 63

84S, 84P, 105

210, 252, 300

315, 336

378, 420









Capacities and Specifications Burner Size
145S 145P 175
Oil Input (U.S.G.P.H.)(See Note 1) 75 90 105
Gas Input (M.BT/HR.)(See Note 2) 10,500 12,600 14,700
Boiler Horsepower @ 80% EFF. (See Note 3) 250 300 350
Maximum Steam Capacity @ 80% EFF. 212 Deg F (LBS./HR.)(See Note 3) 8,628 10,353 12,709
Metering Unit & Compressor Module Motor HP LNDL, LNDLG145 Metering Integral Oil/Air Unit - 3 Phase 2 2 -
LNDM, LNDMG145 Metering Integral Oil/Air Unit - 3 Phase 2 2 -
LNDL, LNDLG175 Oil Metering Unit - 3 Phase - - 1/2
LNDM, LNDMG175 Air Compressor Module - 3 Phase - - 5
LNDE, LNDEG Oil Metering Unit 3 - Phase 1/2 1/2 1/2
Air Compressor Module - 3 Phase 3 3 5
Nozzle Line Heater. LNDM, LNDMG, LNDE, LNDEG 5 KW 5 KW 5 KW
Circulating Loop Oil Pressure Requirements (P.S.I.G.) 15 15 15
Standard Gas Train Size (Inches) 3 3 3
Minimum Gas Pressure Requirements (Inches W.C.)(See Note 4) Train Inlet 19.6 2 PSI 2 PSI
Manifold 7.0 10.0 13.0
Blower Motor Horsepower (See Note 5) Model "S" 15 - -
Model "P" - 25 30
FGR Line Piping Size (Inches) 6 8 8
Recommended Combustion Chamber Dimensions (Inches) Length 84 84 100
Width 46 46 55
Centerline Height 23 23 25
Approx. Shipping Weight 1,600 1,600 1,900
Notes
1. Oil input based on No.2 oil at 140,000 Btu/gal
2. Gas input based on natural gas at 1,000 Btu/cu.ft and 0.60 specific gravity
3. Boiler overall efficiency of 80% estimated. Industrial Combustion does not guarantee overall boiler efficiency.
4. Gas pressures based on zero furnace pressure with standard U.L. train inlet. For total pressure required, add furnace pressure.
5. Impeller and motor H.P. is based on altitudes up to 2000 feet above see level. For impellers and motor sizes at higher altitudes, and 50 cycle applications, consult factory. For higher furnace pressures, consult factory. Standard motor voltages are 208-230-460/3/60.



Type of fuel determines the model designation.
Model Fuel
LNDG Gas
LNDL No. 2 Oil
LNDLG Gas/No. 2 Oil
LNDM No. 2 - 5 Oil
LNDMG Gas/No. 2 - 5 Oil
LNDE No. 2 - 6 Oil
LNDEG Gas No. 2 - 6 Oil



To Top of Page: