H/Series Industrial Combustion Burners
K/Series Industrial Combustion Burners
M/Series Industrial Combustion Burners

Click one the size of burner that you would like to see a diagram on:


42,54,63

84,105

145,175

210,252,300


Capacities & Specifications Burner Size
42 54 63 84 105 145 175 210 252 300
Oil Input (U.S.G..P.H) (See Note 1) 30 38 45 60 75 107 125 150 180 214
Gas Input(M.BTU/HR.) (See Note 2) 4,200 5,400 6,300 8,400 10,500 15,000 17,500 21,000 25,200 30,000
Boiler HorsePower @ 80% EFF. (See Note 3) 100 125 150 200 250 357 417 500 600 700
Max Steam Cap. @ 80% EFF. 212 deg. F (LBS./HR.)(See Note 3) 3,450 4,313 5,175 6,900 8,625 12,316 14,350 17,250 20,700 24,150
Metering Unit & Compressor Module Motor HP DL, DLG Intergral Air/Oil Unit 3 Phase 1 1 1 1 2 2 - 3/4 3/4 3/4
DM, DMG Integral Air/Oil Unit 3 Phase 1 1 2 2 2 - 1/2 5 7 1/2 7 1/2
DE, DEG Oil Metering Unit 115/60/1 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4
Air Compressor Module 3 Phase 2 2 3 3 3 5 5 5 7 1/2 7 1/2
Nozzle Line Heather (DM, DMG, DE, DEG) (23/60/1) 3 KW 3 KW 3 KW 5 KW 5 KW 5 KW 5 KW 7 KW 10 KW 10 KW
Oil Pressure (P.S.I.G.) (See Note 4) DL, DLG, DM, DMG 10 10 10 10 10 10 10 10 10 10
DE, DEG 15 15 15 15 15 15 15 15 15 15
Standard Gas Train Size (Inches) 2 2 1/2 2 1/2 3 3 4 4 4 4 4
Minimum Gas Pressure Requirements (Incehes W.C.) See Note 5) Train Inlet 9.3 8.9 10.9 12.2 16.4 12.9 16.3 23.1 33.7 46.0
Manifold 4.0 4.0 4.0 4.0 4.0 4.0 4.0 6.0 8.0 10.0
Blower Motor Horsepower (See Note 6) Model S: 3 3 5 5 7 1/2 15 20 20 25 40
Model P: 3 5* 5 7 1/2 10 15 20 25 30 40
Recommended Combustion Chamber Dimensions (Inches) Length 56 60 65 74 84 100 108 116 120 132
Width 28 32 34 38 46 55 60 70 84 84
Centerline Height 14 15 16 18 23 25 27 30 30 32
Approximate Shipping Weight (LBS.) 900 950 950 1,050 1,200 1,400 1,500 2,000 2,400 2,700
Optional Control Circuit Transformer Requirements 208/120 V. Or 240-480/120 V. DG, DL, DLG, DM, DMG 1/2 KVA 1/2 KVA 1/2 KVA 1/2 KVA 1/2 KVA - - 1 KVA 1 KVA 1 KVA
DE, DEG 1 1/2 KVA 1 1/2 KVA 1 1/2 KVA 1 1/2 KVA 1 1/2 KVA - - 1 1/2 KVA 1 1/2 KVA 1 1/2 KVA
* 3 hp on DE, DEG


    Notes
  1. Oil input based on 140,000 Btu/gal.
  2. Gas input based on natural gas at 1000 Btu/cu. ft. and 0.65 specific gravity.
  3. Boiler overall efficiency of 80% estimated. Firing rates based on altitudes to 2000 ft. above sea level. For firing rates at higher altitudes, consult factory. Industrial Combustion does not guarantee overall boiler efficiency.
  4. Table shows circulating loop oil pressure.
  5. Gas pressures based on zero furnace pressure with standard U.L. train inlet. For total pressure required, add furnace presure. See IC-986 (1/83)
  6. Impeller and motor hp based on tltitudes up to 2000 ft. above sea level. For impellers and motor sizes at higher altitudes, and 50 cycle applications, consult factory. Standard motor voltages are 208-230/460/60/3.